FIRE FIGHTING CABLES

ITALFIRE BS 6387 CWZ EN 50200 PH120 LSZH

fire resistant LPCB approved

LPCP FIRE RESISTANT - loss prevention certification board

DOWNLOAD

APPLICATION

Fire performance power cable, suitable for fire alarm systems and emergency lighting, designed to maintain circuit integrity under fire conditions according to BS6387 Categories C, W E Z: up to 950° for 3 hours.

SPECIAL FEATURES

EN 60332-1-2, IEC 60331-21 FE 180, EN 50200 PH 120 ANNEX-E,
BS 6387 CWZ, EN 61034-2, EN 60754-1,
EN 60754-2
h

REMARKS

Conform to RoHS directive
Conform to Low-Voltage Directive (LDV) 2014/35/EU

TECHNICAL FEATURES

Operating temperature

-40°C ÷ +70°C

Conductor

Bare Cu Class 1 or 2 DIN VDE 0812 / IEC 60228

Insulation

High performance Silicone Rubber

Core identification

blue, brown, black, grey

Drain wire

Tinned copper

Shield

Aluminium/Polyester 115% coverage

Sheath material

LSZH Colour Red or White

FIRE TEST to BS6387
Fire test category C= 950°C / 3 h | BS 6387 D2 | Test Applied C

Resistance to fire with water | BS 6387 D3 | Test Applied 30 min

Cat. W 650°C for 30 mins 15 min of water | BS 6387 D3 | Test Applied W

Fire resistance with mechanical shock (1 every 30 s) | BS 6387 D4 | Test Applied 15 min

Category X at 650°; Y at 750°; Z at 950° | BS 6387 D4 | Test Applied Z

RESISTANCE to FIRE CEI EN 50200
Category (PH120) temp. 842°C | EN 50200 | Test Applied PH120

Fire resistance with mechanical shock (1 every 5 min) | EN 50200 | Test Applied OK

Resistance to fire with water and shock (1 every 5 m)| EN 50200-E | Test Applied 30 min

Category (temp 842° for 30min, 15 water)| EN 50200-E | Test Applied OK

CPR (DoP) – EU 305/11

NOT APPLICABLE

Loading...